kVA Load Calculator

Progress

Do you know your load and load characteristics?

Is it Single Phase or Three Phase?

Is it IT or Non IT?

Unfortunately we do not currently have any products on our site that match your choice. Please contact our Hardware Sales Team and we will be happy to discuss your requirements.

Tel: +65 6302 0702

Email: salesups.sg@kohler.com

Converting KW to kVA

Three Phase
KW to kVA Conversion

Converting KW to kVA

IT Equipment kVA
Equipment Typical VA Qty
(Max 500)
Total VA
Workstations 200
Workstation With 15" Monitors 300
Workstation With 17" Monitors 300
Server 400
Blade Server 750
Network Hubs 100
Storage Arrays Per Drive 75

Contact our Hardware Sales Team

Tel: +65 6302 0702

Email: salesups.sg@kohler.com

Recommended Products

KVA Value: kVA

Calculator Used:

Email Me My Recommendations

Please note that this result is for indicative purposes only. If you would like us to give you a call to discuss your recommendation please include your phone number in the form below.





Three Phase

  • PW 5000/TP 60-500kVA (Stand-alone 10-50kVA)

    Kohler PW 5000/TP

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    10-50 kVA
    10-50 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Standalone three-phase UPS system available in seven power ratings from 10 to 50kVA and in different
    Read moreCompare
  • PW-8000DPA

    Kohler PW 8000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    10-60 kVA
    10-60 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Three-phase UPS built for low to medium, high density power protection applications. Leading-edge mo
    Read moreCompare
  • PW 9000DPA (Modular 10-250kVA)

    Kohler PW 9000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    30-250 kVA
    30-250 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    A revolutionary rack-mounted uninterruptible power supply designed with ‘hot swap’ modules for futur
    Read moreCompare

Three Phase

  • PW-8000DPA

    Kohler PW 8000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    10-60 kVA
    10-60 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Three-phase UPS built for low to medium, high density power protection applications. Leading-edge mo
    Read moreCompare
  • PW 9000DPA (Modular 10-250kVA)

    Kohler PW 9000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    30-250 kVA
    30-250 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    A revolutionary rack-mounted uninterruptible power supply designed with ‘hot swap’ modules for futur
    Read moreCompare
  • Kohler PW 9250DPA

    Kohler PW 9250DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    True modular uninterruptible power supply, scalable from 50kW up to 1.5MW, for medium power applicat
    Read moreCompare

Three Phase

  • PW 6000 (Stand-alone 250-300kVA)

    Kohler PW 6000

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    60-500 kVA (500kW)
    60-500 kVA (500kW)
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Transformerless 3 phase UPS from 60kVA to 500 kVA, parallelable up to 5mVA. Offers unrivalled protec
    Read moreCompare
  • PW-8000DPA

    Kohler PW 8000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    10-60 kVA
    10-60 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Three-phase UPS built for low to medium, high density power protection applications. Leading-edge mo
    Read moreCompare
  • PW 9000DPA (Modular 10-250kVA)

    Kohler PW 9000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    30-250 kVA
    30-250 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    A revolutionary rack-mounted uninterruptible power supply designed with ‘hot swap’ modules for futur
    Read moreCompare
  • Kohler PW 9250DPA

    Kohler PW 9250DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    True modular uninterruptible power supply, scalable from 50kW up to 1.5MW, for medium power applicat
    Read moreCompare

Three Phase

  • PW 6000 (Stand-alone 250-300kVA)

    Kohler PW 6000

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    60-500 kVA (500kW)
    60-500 kVA (500kW)
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Transformerless 3 phase UPS from 60kVA to 500 kVA, parallelable up to 5mVA. Offers unrivalled protec
    Read moreCompare
  • PW-8000DPA

    Kohler PW 8000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    10-60 kVA
    10-60 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Three-phase UPS built for low to medium, high density power protection applications. Leading-edge mo
    Read moreCompare
  • PW 9000DPA (Modular 10-250kVA)

    Kohler PW 9000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    30-250 kVA
    30-250 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    A revolutionary rack-mounted uninterruptible power supply designed with ‘hot swap’ modules for futur
    Read moreCompare
  • Kohler PW 9250DPA

    Kohler PW 9250DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    True modular uninterruptible power supply, scalable from 50kW up to 1.5MW, for medium power applicat
    Read moreCompare
  • PW 9500DPA (Modular 100-500kVA)

    Kohler PW 9500DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    100-500 kVA
    100-500 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    Innovative 5 x 100kW modular UPS system offering pay-as-you-grow scalability combined with 99.9999%
    Read moreCompare

Three Phase

  • PW 6000 (Stand-alone 250-300kVA)

    Kohler PW 6000

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    60-500 kVA (500kW)
    60-500 kVA (500kW)
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Transformerless 3 phase UPS from 60kVA to 500 kVA, parallelable up to 5mVA. Offers unrivalled protec
    Read moreCompare
  • PW 9000DPA (Modular 10-250kVA)

    Kohler PW 9000DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    30-250 kVA
    30-250 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    A revolutionary rack-mounted uninterruptible power supply designed with ‘hot swap’ modules for futur
    Read moreCompare
  • Kohler PW 9250DPA

    Kohler PW 9250DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    True modular uninterruptible power supply, scalable from 50kW up to 1.5MW, for medium power applicat
    Read moreCompare
  • PW 9500DPA (Modular 100-500kVA)

    Kohler PW 9500DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    100-500 kVA
    100-500 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    Innovative 5 x 100kW modular UPS system offering pay-as-you-grow scalability combined with 99.9999%
    Read moreCompare

Three Phase

  • PW 6000 (Stand-alone 250-300kVA)

    Kohler PW 6000

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    60-500 kVA (500kW)
    60-500 kVA (500kW)
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Standalone
    Standalone
    Standalone UPS systems allow several units to be operated in tandem (known as horizontal scaling) to provide for a greater load.
    Transformerless 3 phase UPS from 60kVA to 500 kVA, parallelable up to 5mVA. Offers unrivalled protec
    Read moreCompare
  • PW 9500DPA (Modular 100-500kVA)

    Kohler PW 9500DPA

    Three Phase PW
    Three Phase PW
    A three-phase installation uses the full three phases which are generated from the grid. A three phase electrical supply comprises of three individual sine waves, and can be installed as either a three wire or three wire & neutral configuration. A three-phase source would typically come from a local transformer, with the standard three phase voltage being 400/415 VAC.
    100-500 kVA
    100-500 kVA
    Understanding the total kVA requirement of a critical load is a key part of establishing a UPS’ true sizing requirement. For more information see kVA calculator and guide to choosing a UPS.
    Modular
    Modular
    UPS systems such as the PW 9000DPA Series are configured by plugging up to five modules into a 19” rack to meet the capacity and redundancy requirement of the application load. This provides more flexibility and scalability than a complete cabinet containing a single standalone system.
    Innovative 5 x 100kW modular UPS system offering pay-as-you-grow scalability combined with 99.9999%
    Read moreCompare

Top

Pin It on Pinterest

Share This